Honeywell SMV 3000 Satellite Radio User Manual


 
1/99 SMV 3000 Transmitter Users Manual 169
A.6 Operation Notes, Continued
Status Messages
Supplement the IOP status messages given in Section 8 of the PM/APM
Smartline Transmitter Integration Manual with those listed in Table A-13.
Note that the displayed status messages will be the same for all slots (PVs)
associated with a given SMV 3000 transmitter.
Table A-13 Additional IOP Status Messages
Message Problem Corrective Action
COMMAND ALLOWED ONLY
ON FIRST SLOT OF
MULTIPLE PV XMTRS
Attempted to download database
with DECONF change from slot
2, 3, or 4.
Call up slot 1 Detail display for PV1
and retry database download
command.
COMMAND FAILURE
. . . BUSY
Command could not be executed
because transmitter is busy
Retry command.
CONFIGURATION MISMATCH
MULTIPLE DEVICES
ASSIGNED TO SLOT
Another transmitter is physically
connected to a logical slot for a
multivariable transmitter.
Disconnect offending transmitter or
reconfigure the number of PVs for the
SMV 3000 transmitter.
TRANSMITTER IS
BROADCASTING A
SUBSTITUTE VALUE PV
Transmitter is in output mode or
input mode.
Use SCT 3000 to remove transmitter
from output mode or input mode.
Bad PV Indication
In most cases, configuration error detection will result in a Bad PV (BP)
indication for all slots (PVs) associated with a given SMV 3000
transmitter. However, if the number of IOP slots allocated differs from the
number of PVs configured in the SMV 3000 transmitter, only the slots
reserved by the IOP will be flagged as bad. A download command from
slot 1 usually clears Bad PV indication from all but the offending slot
(PV). You will have to make configuration changes to resolve slot
conflicts.