Mitsubishi Electronics MR-J2-03A5 Stereo Amplifier User Manual


 
5 - 11
5. PARAMETERS
Class No. Symbol Name and Function
Initial
Value
Unit
Setting
Range
Control
Mode
Expansion parameters
22 *OP4 Function selection 4:
Used to select stop processing at LSP/LSN signal off and choose the
machine resonance suppression filter.
Machine resonance suppression filter
How to make a stop when LSP/LSN
signal is valid.
0: Sudden stop
1: Slow stop
In the position control mode,
the servo motor is decelerated
to a stop according to parameter
No. 7 setting.
In the speed control mode,
the servo motor is decelerated
to a stop according to parameter
No. 12 setting.
Set Value
0
1
2
Filtering Time [ms]
0
1.77
3.55
37.11
Set Value
0
1
2
Notch Frequency [Hz]
Not used
1125
563
3 375
4
5
6
282
225
188
7 161
0
VC/VLA voltage averaging
Used to set the filtering time when the
analog speed command (VC) voltage or
analog speed limit (VLA) is imported.
Set 0 to vary the speed to voltage fluctua-
tion in real time. Increase the set value
to vary the speed slower to voltage flu-
ctuation.
0000 0000h
to
7301h
P x S x T