Paradise 205486 REV F Stereo Amplifier User Manual


 
52 205486 REV F Operations Manual, HPA2, Compact Outdoor SSPA
7.1.2.2 PC Control using RS232 and Paradise Universal M&C Software
In applications requiring remote monitor and control of the redundant system, the Paradise
Datacom Universal M&C program has a control panel that can be used for this purpose. To
enable the 1:1 system to operate with the remote control software, first configure each
amplifier for 1:1 redundant operation as previously described in the Stand-Alone 1:1
Redundant System section.
When using RS232, a separate COM port will be required for each amplifier. Therefore a
computer with at least two COM ports is required for such a system. Systems using RS232
are limited by the length of the communication cable from the amplifiers to the computer. This
is typically a maximum of 30 ft. (9 m) for most RS232 device drivers. Systems requiring longer
communication cable links should use RS485 communication.
After starting the M&C program, select “Action” “Add Unit” “Compact Outdoor SSPA”.
See Figure 7-9. The Add New SSPA window will appear as shown in Figure 7-10.
Figure 7-9: Adding a SSPA Monitor and Control Window