iCOM
Control Training and Service Manual
048 Unit 7
disconnected
" Warning no no -
049 Unit 8
disconnected
" Warning no no -
050 Unit 9
disconnected
" Warning no no -
051 Unit 10
disconnected
" Warning no no -
052 Unit 11
disconnected
" Warning no no -
053 Unit 12
disconnected
" Warning no no -
054 Unit 13
disconnected
" Warning no no -
055 Unit 14
disconnected
" Warning no no -
056 Unit 15
disconnected
" Warning no no -
057 Unit 16
disconnected
" Warning no no -
058 COMP 2 HIGH
PRESSURE
Compressor 2 stopped
because of high pressure
Alarm no yes yes
(broken co
will remain
off)
059 COMP 2 LOW
PRESSURE
Compressor 2 stopped
because of low pressure
Alarm no yes yes
(broken co
will remain
off)
060 COMP 2 HRS
EXCEEDED
actual working hours of
compressor 2 are higher
than the threshold set.
Warning no no -
062 FREECOOL
TEMP
SENSOR
sensor faulty or not
present, but needed from
control (freecooling
control enabled).
Warning no no -
064 ON-OFF KEY
DISABLED
the display on-off button
was set disabled but
somebody pressed it.
Warning no no -
070 NO
CONNECTION
w/Unit1
the unit showing this
event has no connection
to the unit #1.
Warning no no -
071 COMP 1
OVERLOAD
Compressor 1 stopped
because of overload
Alarm no yes yes
(broken co
will remain
off)
95