iCOM
Controls Training and Service Manual
Service Menu: System / Network Setup Parameters Series S800:
Page 2 of 2, Unit View
Menu Line Function Default Range
S834 Password -
S835 Monitoring Protocol - -
S836 IP Address - IP Range
S837 Netmask - Netmask Range
S838 Gateway - Gateway Range
S839 MAC - MAC Range
S840 U2U Protocol - 33 - 64
S841 U2U Address - -
S842 -
S843 Bootloader Variables Status - Changed, Updating
S844 Bootloader Variables Control - No, Save + Reboot
Service Menu: Option Setup Parameters S400 series: Page 1 of 2
Menu Line Function Default Range
S401 Password - -
S402 Compressor Sequence Auto 1, 2, Auto
S403 Low Pressure Delay (WSK) 3 0 – 5 Minutes
S404 Actual LP1 Pressure - 14.5 – 87.0 psiA
S405 Actual LP2 Pressure - 14.5 – 87.0 psiA
S406 Electric Stages - 0, 1, 2, 3
S407 Hot Water Heat On / Off No No or Yes
S408 Hot Gas Heat No No, Comp. 1, Comp. 2
S409 Total Heat Stages No 0, 1, 2, 3l
S410 3P Actuator Runtime 165 Seconds 50 – 400 seconds
S411 3P Actuator Direction Direct Direct or Reverse
82