iCOM
Control Training and Service Manual
Advanced Menu: Factory Settings Parameters A100 series: Page 2 of 6
Advanced Menu: Factory Settings Parameters A100 series: Page 3 of 6
Menu Code Function Default Range
A101 Password - -
A102 Refrigerant Type R22 R22, R407C
A103 Main Fan Overload Shut down Shut down, Disable
A104 Loss of Airflow Shut down Shut down, Disable
A105 Number of Compressors 2 0, 1, 2
A106 Compressor Delay Time 0 0 - 120 Sec
A107
Compressor Minimum
On Time
3 Min 0 - 5 Min
A108
Compressor Minimum
Off Time
3 Min 0 - 5 Min
A109 Pump Down Yes No, Yes
A110 Capacity Control Type Unloader
No, Unloader, HGBP,
Digital, Digital + TH
Menu Code Parameter Default Range
A112 Password - -
A113 Digi Scroll Cycle 15 No, 10 - 30 Sec
A114
High Temperature Digi
Scroll
268°F 33 - 392°F
A115 Digi Scroll Switchback 250°F 33 - 392°F
A116
Low Pressure Device
Type
Analog Analog, Switch
A117
Low Pressure Threshold
Phase 1
* See Note 1 0.0 - 145 psiA
A118
Low Pressure Threshold
Phase 2
* See Note 2 0.0 - 145 psiA
85