iCOM
Controls Training and Service Manual
028 HUM HRS
EXCEEDED
actual working hours of
the fan are higher than
the threshold set.
Warning no no -
029 SUPPLY
SENSOR
FAILURE
sensor faulty or not
present, but needed from
control (supply limit
control enabled).
Warning no no -
031 ROOM
SENSOR
FAILURE
no valid data from the
std. sensor
Alarm yes yes no
032 SENSOR A
FAILURE
no valid data from sensor
A
Warning no no -
034 NETWORK
FAILURE
the unit showing this
event has no connection
to the unit #1.
Warning no no -
036 UNIT ON fan motor in operation Message - - -
037 UNIT OFF unit shut down Message - - -
038 SLEEP MODE unit is in sleep mode:
according to the settings
it is switched off or
working with a selectable
deadband.
Message - - -
039 STANDBY
MODE
unit is in standby (fan
off), waiting for a call to
start from the system (if
a unit fails or there is a
bus interruption).
Message - - -
040 POWER ON control is powered again
after a power off.
Message - - -
041 POWER OFF no power to the control:
this message will appear
at the next power on.
Message - - -
042 Unit 1
disconnected
this event is created from
a coldfire display only:
the display doesn't find
unit #1
Warning no no -
043 Unit 2
disconnected
" Warning no no -
044 Unit 3
disconnected
" Warning no no -
045 Unit 4
disconnected
" Warning no no -
046 Unit 5
disconnected
" Warning no no -
047 Unit 6
disconnected
" Warning no no -
94