iCOM
Control Training and Service Manual
Large Display Jumper Settings
Jumper Type Setting
P3 Watchdog * Shunt on Pins 1 & 2
P4
Manual Contrast
(Rev. 1)
* Shunt on Pins 2 & 3
P8 open * open
P13 open * open
P78 CAN Termination * Shunt on Pins 2 & 3
P82
Watchdog
(Rev. 2 Only)
* Shunt on Pins 1 & 2
P83 Bootloader * Shunt on Pins 2 & 3
* Default Setting
Small Display DIP Switch #3 Settings
Position Type Setting
1 CAN Address Off
2 CAN Address Off
3 CAN Address Off
4 CAN Address Off
5 CAN Address On
6 CAN Address On
7 CAN Baud Off
8 CAN Baud Off
105