iCOM
Controls Training and Service Manual
iCOM Control Board Jumper Settings
Jumper Type Setting
P19 Watchdog
* On: Shunt on Pins 1 & 2
Off: No Shunt
P78
CAN Bus
Terminator
On: Shunt on Pins 2 & 3
* Off: Shunt on Pins 1 & 2
P83 Bootloader
Enabled: Shunt on Pins 1 & 2
* Disabled: No Shunt
* Default Setting
Large Display DIP Switch #3 Settings
Position Type Setting
1 CAN Address Off
2 CAN Address Off
3 CAN Address Off
4 CAN Address Off
5 CAN Address Off
6 CAN Address Off
7 CAN Baud Off
8 CAN Baud Off
104