Controls Training and Service Manual
Service Menu: Set Alarm Parameters S200 series: Page 1 of 6
Menu Line Parameter Default Range
S201 Password - -
S202 Return Sensor Alarms Enabled Disabled or Enabled
S203 High Return Temperature 80ºF 34 - 210ºF
S204 Low Return Temperature 65ºF 34 - 210ºF
S205 High Return Humidity 60% 1 – 99%
S206 Low Return Humidity 40% 1 – 99%
S207 Sensor A Alarms Disabled Disabled or Enabled
S208 High Temperature Sensor A 90ºF 34 - 210ºF
S209 Low Temperature Sensor A 55ºF 34 - 210ºF
S210 High Humidity Sensor A 70% 1 – 99%
S211 Low Humidity Sensor A 30% 1 – 99%
Service Menu: Set Alarm Parameters: Page 2 of 6
Menu Line Parameter Default Range
S212 Password - -
S213 Customer Input 1 Water alarm See note
S214 Customer Input 1 Active When Closed Open or Closed
S215 Customer Input 2 Water alarm See note
S216 Customer Input 2 Active When Closed Open or Closed
S217 Customer Input 3 Water alarm See note
S218 Customer Input 3 Active When Closed Open or Closed
S219 Customer Input 4 Water alarm See note
S220 Customer Input 4 Active When Closed Open or Closed
S221 Warning Activates Alarm Relay Yes Yes or No
S222 Reset Disabled Alarms No Yes or No
Note: Customer Inputs 1, 2, 3 and 4 messages may be selected from Smoke
Detected, Water Alarm, Condensate Pump Alarm, Flow Alarm, Standby Pump,
Standby Unit.
76