Control Training and Service Manual
Service Menu Parameters
The Service menu display allows the user to customize the various unit settings for
site specific operation. The factory default password to access the service menu
items for programming is “501”. The Service Menu selections include the following
choices in the order shown:
Set Point Parameters
Unit Diary
Standby Settings Parameters
Maintenance / Wellness Setting Parameters
Diagnostic / Service Mode Parameters
Set Alarm Parameters
Sensor Calibration / Setup Parameters
System / Network Setup Parameters
Operations Setup Parameters
Service Contacts Parameters
Service Menu: Set Point Parameters S100 series: Page 1 of 2
Menu Line Parameter Default Range
S101 Password - -
S102 Temperature Setpoint 73ºF 41 - 104ºF
S103 Humidity Setpoint 50% 1 – 80%
S104 Humidity Control Type Yes Yes or No
S105 Supply Limit Disabled Disabled or Enabled
S106 Supply Limit Temp Value 41ºF 41 - 77ºF
S107 Autoset Enable Yes Yes or No
S108 Temperature Proportional Band 7ºF 2 - 54ºF
S109 Temperature Integration Time 0 0 – 5 minutes
S110 Temperature Deadband 0 0 - 36ºF
S111 Short Cycle Control Yes Yes or No