Advanced Menu: Factory Settings Parameters: Page 4 of 6
Advanced Menu: Factory Settings Parameters A100 series: Page 5 of 6
Menu Code Parameter Default Range
A123 Password - -
A124 LP1 Sensor 10% 0 - 100%
A125
LP1 Signal 150 psiA -87.0 to +725 psiA
A126 Actual LP1 Signal - 0 - 100%
A127 LP2 Sensor 10% 0 - 100%
A128
LP2 Signal 150 psiA -87.0 to +725 psiA
A129 Actual LP2 Signal - 0 - 100%
A130 Pumpdown Cutout 35 psiA 0.0 - 145 psiA
A131 Pumpdown Recycle 80 psiA 0.0 - 145 psiA
A132
Heat Rejection Control
Type
Fan Speed
Fan Speed /
Lee-Temp / Glycol
Menu Code Parameter Default Range
A134 Password - -
A135
A136 CW flush Duration 0 No, 1 - 3 min
A137 Freecooling
No
No, Yes
A138
A139 Freecooling Flush Duration 0 No, 1 - 3 min
A140 Freecooling Flush Starts R5 Yes No, Yes
A141 CO + FC simultaneously Yes No, Yes
A142
A143 Hot water flush duration 0 No, 1 - 3 min