iCOM
Controls Training and Service Manual
Events Notifications Parameters (continued)
ID Type Description (Large Display) Description (Small Display)
111 Warning
EL.HEAT 1 HOURS
EXCEEDED
EL.HEAT 1 HOURS EXC.
112 Warning
EL.HEAT 2 HOURS
EXCEEDED
EL.HEAT 2 HOURS EXC.
113 Warning
EL.HEAT 3 HOURS
EXCEEDED
EL.HEAT 3 HOURS EXC.
Event ID number, Description and Function
ID Description Event explanation Default
Type
Shut
down
single
unit
Rotat
e
stand
by
restart if
duty unit
fails also
000 GENERAL
ALARM
Warning or Alarm was
acknowledged or reset
Reset - - -
001 COMP 1 HIGH
PRESSURE
Compressor 1 stopped
because of high pressure
Alarm no yes yes
(broken co
will remain
off)
002 COMP 1 LOW
PRESSURE
Compressor 1 stopped
because of low pressure
Alarm no yes yes
(broken co
will remain
off)
003 HIGH CW
TEMP
chilled water temperature
too high (input from
thermostat)
Warning no no -
004 LOSS OF CW
FLOW
chilled water flow too low
(input from flow switch)
Warning no no -
005 EL HEAT HIGH
TEMP
electric heaters stopped
because of too high
temperature on the
safety thermostat
Warning no no -
006 MAIN FAN
OVERLOAD
fan motor protection has
stopped the fan due to
overload.
this event can be set to
switch off the unit or to
disable hum and electric
heat.
Alarm yes, if
set to
shut
down
yes yes, only if
set to
"disable"
92