Control Training and Service Manual
Service Menu: Set Alarm Parameters: Page 3 of 6
Menu Line Parameter
S223 Password
S224 DELAY EN-DIS TYPE
S225 Main Fan Overload 10 Sec En Alarm
S226 Loss of Airflow 10 Sec En Alarm
S227 Clogged Filters 60 Sec En Warning
S228 High Room Temperature 10 Sec En Warning
S229 Low Room Temperature 10 Sec En Warning
S230 High Room Humidity 10 Sec En Warning
S231 Low Room Humidity 10 Sec En Warning
S232 High Temp Sensor A 10 Sec En Warning
S233 Low Temp Sensor A 10 Sec En Warning
S234 High Humid Sensor A 10 Sec En Warning
S235 Low Humid Sensor A 10 Sec En Warning
Service Menu: Set Alarm Parameters: Page 4 of 6
Menu Line Parameter
S236 Password
S237 DELAY EN-DIS TYPE
S238 Comp 1 Overload 10 Sec En Alarm
S239 Comp 2 Overload 10 Sec En Alarm
S240 Comp 1 High Pressure - En Alarm
S241 Comp 1 High Pressure - En Alarm
S242 Comp 1 Low Pressure - En Alarm
S243 Comp 2 Low Pressure - En Alarm
S244 Comp 1 Pumpdown Fail - En Alarm
S245 Comp 2 Pumpdown Fail - En Alarm
S246 Dig Scroll1 High Temp - En Alarm
S247 Dig Scroll2 High Temp Alarm