iCOM
Control Training and Service Manual
User Menu: Set Point Parameters U100 series
Menu Line Parameter Default Range
U101 Password - -
U102 Temperature Setpoint 73ºF 41 - 104ºF
U103 Humidity Setpoint 50% 1 – 80%
U104 Humidity Control Type Yes Yes or No
U105 Supply Limit Disabled Disabled or Enabled
U106 Supply Limit Temp Value
41°F 41 - 77°F
U107
U108
U109
U110
U111
User Menu: Spare Parts List, Large Display Only
Parameter
Unit spare parts list
User Menu: Event Log
Parameter
Stores the last 400 events (messages, warnings and
alarms a that have occurred
61