Liebert TM-10098 Stereo System User Manual


 
iCOM
Control Training and Service Manual
6. Each set of unit control boards must be set up individually, then connected to
the network switch and checked before the next board can be setup
6a. Large Displays and Control Boards must each be programmed with a
different IP Address.
Example: Display: 192.168.254.001
Example: Control Board: 192.168.254.010
6b. Each Display and Control Board in the iCOM network must have the
same Gateway IP address.
Example: Gateway IP: 192.168.254.75
6c. Each Display and Control Board in the iCOM network must have the
same Netmask IP address.
Example: Netmask IP = 255.255.255.000
6d. The Unit to Unit (U2U) address must be programmed in the necessary
order for setup.
Example: Unit Display: 33 – 64 and Unit Control Board: 1 - 32
43