A.5 Configuring Smart Meter Using Pushbuttons, Continued
Setting Lower Display
Values, continued
Table A-7 Setting Lower Display Values for Smart Meter Display
Step Action Meter Display
1 You have completed units selection in Table
A-5 and U-L appears on the display. Press
LOWER VALUE button to initiate lower
display limit setting function.
ATTENTION
This procedure is only
applicable for Custom (EUF) engineering unit
selection in a transmitter configured for
LINEAR output conformity.
The lower display value for transmitters
configured for SQUARE ROOT output
conformity is fixed at zero (0.00) and cannot
be changed.
If lower limit display value was previously set,
KNOWN VALUE indicator lights and set value
flashes in display.
%
1000
ANALOG
UPPER
VALUE
UNITS
LOWER
VALUE
SET
VAR
SEL.
0. 00
Previously set
value flashes in
display and
indicator lights
KNOWN VALUE
2 Press LOWER VALUE button again within 5
seconds. Otherwise, meter exits limit setting
function.
Display shows magnitude range selection.
%
1000
ANALOG
UPPER
VALUE
UNITS
LOWER
VALUE
SET
VAR
SEL.
19 .99
ATTENTION
The magnitude range
selection only applies for setting the display
limits. This selection does not affect the
normal operation of the meter. During normal
operation, the display is automatically ranged
to provide the best precision possible.