Honeywell ST 3000 Satellite Radio User Manual


 
A.4 Setting Range Values (Local Zero and Span), Continued
Procedure, continued
Table A-3 Setting Range Values Using Local Zero and Span
Adjustments, Continued
Step Action
10
Wait 30 seconds so that changes have been copied to the
transmitter’s non-volatile memory.
11
Remove applied pressure and turn OFF transmitter power.
12
Replace end-cap on PWA side of electronics housing and tighten
lock.
13
Remove milliammeter from TEST terminals and replace end-cap and
tighten lock.
14
Turn ON transmitter power and check smart meter reading, if
applicable.
Figure A-2 Typical Setup for Setting Range Values Using Local Zero and Span Adjustments.
Smart Meter with
Local Zero and Span
installed on PWA side
of electronics housing
UPPER
VALUE
UNI T S
LOWER
VALUE
SET
VAR
SEL.
SPA N
ZERO
%
10 0
0
0
A
NALOG
In H O
2
00
-
S
I
G
N
A
L
+
+
-
T
E
S
T
Power
Supply
+
-
Receiver
+
-
Field
Terminals
ST 3000
250 ohm
Milliammeter
58 ST 3000 Release 300 Installation Guide 2/05