Honeywell ST 3000 Satellite Radio User Manual


 
10/04 34-ST-99-36 (Addendum to 34-ST-33-39) 5 of 10
Specific Parameters
for Intrinsic Safety
Field wiring terminals, (+ , ):
Without local analog meter, ME:
With local analog meter, ME:
With local smart digital meter, SM:
Ui = 30 V, Ii = 100 mA, Pi = 1.2 W
Ci = 4.2 nF, Ri = 0, Li = 0
Ci = 4.2 nF, Ri = 0, Li = 150 µH
Ci = 4.2 nF, Ri = 0, Li = 0
The pressure transmitter is an intrinsically safe apparatus that can be installed in
potentially explosive atmospheres.
The power terminals (+, -) must be connected only to a certified associated
intrinsically safe apparatus.
The electrical parameters (U, I, and P) of the associated apparatus connected to the
power terminals (+, -) must not exceed the following values:
Ui 30V
Ii 100 mA
Pi 1,2 W
Ambient temperature: - 50ºC to 93ºC
NOTE: -50ºC to 93ºC is the certification and “Operative Limits” for the product
family. Refer to individual Specification Sheets for the standard “Rated Condition”
ambient limits for a particular model that, as shown on the data-plate and
certification nameplate, may be less than the certification limits.
Temperature classifications:
IS (ia) 4 – 20 mA / DE
T4 up to Ta 93ºC
T5 up to Ta 85ºC
T6 up to Ta 70ºC
Flameproof (d)
T5 up to Ta 93ºC
T6 up to Ta 78ºC
Special conditions
for safe use,
Intrinsic Safety (X)
Enclosure classification: IP 66/67, Type 4X
Specific Parameters
for Flameproof
Installation
Power supply to field wiring terminals, (+, ): Ucc 42 V
Output Signal: 4–20 mA
Special conditions
for safe use,
Flameproof
Installation
Ambient operating temperature: - 50 to 93ºC
NOTE: -50ºC to 93ºC is the certification and “Operative Limits” for the product family.
Refer to individual Specification Sheets for the standard “Rated Condition” ambient
limits for a particular model that, as shown on the data-plate and certification
nameplate, may be less than the certification limits.