Toshiba MMU-AP0181MH Cassette Player User Manual


 
38
No.
15
Outline of specifications
<Operation standby> .......... Display on remote controller
1. •“P05 is one of displays of power wire missing.
•“P05 of power cable is detected.
•“COOL/DRY operation cannot be performed because the
other indoor unit is under HEAT operation.
•“HEAT operation cannot be performed because COOL
priority is set (Outdoor I/F P.C. board SW11 1-bit is ON)
and the other indoor unit is under COOL/DRY operation.
•“FAN operation cannot be performed because the system
performs Heat oil/Refrigerant recovery operation.
There is a unit in which indoor overflow P10 is detected.
There is a unit in which interlock alarm P23 is detected.
2. The above indoor units unavailable to operate waits under
condition of thermostat OFF.
<HEAT standby> .................. Display on remote controller
1. During HEAT operation, the fan rotates with lower air speed
than one specified in order to prevent discharge of cold
draft or stops. (including case that defrost operation is
being performed)
•“HEAT operation cannot be performed because COOL
priority is set (Outdoor I/F P.C. board SW11 bit 1 is ON) and
the other indoor unit is under COOL/DRY operation.
2. HEAT standby is displayed until the above conditions are
released.
Remarks
•“ goes on.
Item
and
display
(Operation and
heating stand-by)
•“
goes on.
16 Selection of
central control
mode
1. The contents which can be changed on the remote controller
at indoor unit side can be selected by setup at the central
controller side.
2. In case of operation from TCC-LINK central controller
(TCB-SC642 TLE2, etc.)
[Central control mode 1] : Cannot operate
[Central control mode 2] :
Cannot operate, stop, select mode, set up temp.
[Central control mode 3] :
Cannot select mode, set up temp.
[Central control mode 4] : Cannot select mode
3. RBC-AMT31E (Wired remote controller)
While mode is the central control mode,
CENTRAL
lights on the display part of the remote controller.
If operation is performed
from the remote control
CENTRAL CONTROL
mode, the status is
notified with receiving
sound.