Toshiba MMU-AP0181MH Cassette Player User Manual


 
36
E
B
A
A zone: OFF
B zone:
Over 26˚C, below 28˚C, ULTRA LOW
C zone:
Over 28˚C, below 30˚C, LOW
D zone:
Over 30˚C, below 32˚C, MED
E zone: HIGH
D
C
32
30
28
26
20
16
(˚C)
No.
6
Outline of specifications
1. In all heating operation, the upper limit of the fan tap is set by
one with higher temperature of TC2 sensor and TCJ sensor.
When B zone has continued for 6 minutes, the operation
shifts to C zone.
In defrost time, the control point is set to +6°C.
Remarks
In D and E zones, priority
is given to remote control-
ler air speed setup.
In A
is displayed.
Item
Prevention of
cold air
discharge
7 Freeze
prevention
control (Low
temp. release)
1. In all cooling operation, the air conditioner operates as de-
scribed below based upon temp. detected by TC1, TC2 and
TCJ sensors.
To prevent the heat exchanger from freezing, the operation
stops.
When J zone is detected for 5 minutes, the command
frequency becomes S0 to the outdoor unit.
In K zone, the timer count is interrupted, and held.
When 1 zone is detected, the timer is cleared and the
operation returns to the normal operation.
When the command frequency became S0 with continua-
tion of J zone, operation of the the indoor fan in LOW
mode until it reaches the 1 zone.
It is reset when the following conditions are satisfied.
Reset conditions
1) TC1
>
12°C and TC2
>
12°C and TCJ
>
12°C
2) 30 minutes passed after stop.
2. In all cooling operation, the air conditioner operates as
described below based upon temp. detected by TC2 and TCJ
sensors.
When M zone is detected for 45 minutes, the command
frequency becomes S0 to the outdoor unit.
In N zone, the timer count is interrupted and held.
When shifting to M zone again, the timer count restarts
and continues.
If L zone is detected, the timer is cleared and the opera-
tion returns to normal operation.
Reset conditions
1) TC1
>
12°C and TC2
>
12°C and TCJ
>
12°C
2) 30 minutes passed after stop.
In a Model without TC2,
TC2 is not judged.
P2
Q2
TC2, TCJ
5°C
2.0°C
P1
Q1
(˚C)
a
K
J
P2
Q2
(˚C)
L
N
M
( ) value:
When the power supply is
turned on, the Forced
thermo becomes OFF if the
temperature is less than this
indicated temperature.
P1
Q1
TC1
10°C (5°C)
0°C
TC2, TCJ
–10°C
–14°C