Mitsubishi Electronics A8GT-J61BT15 Stereo Equalizer User Manual


 
4 - 25 4 - 25
MELSEC-GOT
4 MONITORING SPECIFICATION
(3) Communication overview
When always reading the data in the GOT internal device GD100, 200, and 300
to the remote register.
0603
H
RWw0
1) 2)
0064
H
00C8
H
012C
H
RWw1
RWw2
RWw3
1234
H
RWw0
0E54
H
0066
H
RWw1
RWw2
FROM
0603
H
RWw0
0064
H
00C8
H
012C
H
RWw1
RWw2
RWw3
1234
H
RWw0
0E54
H
0066
H
RWw1
RWw2
1234
H
GD100
0E54
H
GD200
GD300
0066
H
TO
5)
4)
3)
GOT internal device
GOT monitor request flag
3)
Monitor
register
command
Monitor
requeset
command
PLC CPU
Master station
remote register
GOT
remote register
1) Store the monitor register command data in the master station's remote
register (RWw).
2) Turn on the GOT request flag, and store the command data in the GOT
remote register (RWw).
(Command execution)
The GOT complete flag turns on when the command processing is complete.
3) By turning on the GOT monitor request flag, always read the data in the
GD100, 200 and 300 to the remote register (RWr).
4) By link scan, the read data is stored in the master station’s remote register
(RWr).
5) Read the data to the PLC CPU using the FROM instruction, etc.