Emerson 1700 Satellite Radio User Manual


 
Installation Manual 63
Specifications
Output Wiring – Configurable I/O SpecificationsOutput Wiring – Fieldbus/PROFIBUSOutput Wiring – Intrinsically Safe Output Wiring – Configurable I/O SpecificationsOutput Wiring – Fieldbus/PROFIBUSOutput Wiring – Intrinsically Safe Output Wiring – Configurable I/O SpecificationsOutput Wiring – Fieldbus/PROFIBUSOutput Wiring – Intrinsically Safe Output Wiring – Configurable I/O SpecificationsOutput Wiring – Fieldbus/PROFIBUSOutput Wiring – Intrinsically Safe
A.2 Hazardous area classifications
The transmitter may have a tag listing hazardous area classifications, which indicate suitability for
installation in the hazardous areas described in this section.
A.2.1 UL and CSA
Ambient temperature is limited to –40 to +131 °F (–40 to +55 °C) for UL compliance.
Ambient temperature is limited to –40 to +140 °F (–40 to +60 °C) for CSA compliance.
Transmitter
Class I, Division 1, Groups C and D. Class II, Division 1, Groups E, F, and G explosion proof (when
installed with approved conduit seals). Otherwise, Class I, Division 2, Groups A, B, C, and D.
Outputs
Provides nonincendive sensor outputs for use in Class I, Division 2, Groups A, B, C, and D; or
intrinsically safe sensor outputs for use in Class I, Division 1, Groups C and D or Class II, Division 1,
Groups E, F, and G.
A.2.2 ATEX and IECEx
Ambient temperature is limited to below 131 °F (55 °C) for ATEX and IECEx compliance. Table A-1
lists the classification codes for each transmitter output option.
Table A-1 ATEX and IECEx classifications
Output option Classification ATEX IECEx
Analog,
non-incendive
FOUNDATION fieldbus,
and configurable I/O
(output options A, N, B, and C)
Flameproof when installed with
approved cable glands:
With display EEx d [ib] IIB+H2 T5 Ex d [ib] IIB+H2 T5
• Without display EEx d [ib] IIC T5 Ex d [ib] IIC T5
Increased safety when installed
with approved cable glands:
• With display EEx de [ib] IIB+H2 T5 Ex de [ib] IIB+H2 T5
• Without display EEx de [ib] IIC T5 Ex de [ib] IIC T5
Intrinsically safe analog,
intrinsically safe F
OUNDATION
fieldbus, and PROFIBUS-PA
(output options D, E, and G)
Flameproof when installed with
approved cable glands:
• With display EEx d [ia/ib] IIB+H2 T5 Ex d [ia/ib] IIB+H2 T5
• Without display EEx d [ia/ib] IIC T5 Ex d [ia/ib] IIC T5
Increased safety when installed
with approved cable glands:
• With display EEx de [ia/ib] IIB+H2 T5 Ex de [ia/ib] IIB+H2 T5
• Without display EEx de [ia/ib] IIC T5 Ex de [ia/ib] IIC T5