Model 1700 and 2700 Transmitters
Specifications
One or two frequency/pulse outputs:
Channels B and C are configurable as frequency/pulse outputs
If both are configured for frequency/pulse:
- The channels function as a dual-pulse output which reports a single process variable.
Channels are electrically isolated but not independent
- Output on channel C can be phase-shifted 0, 90, or 180 degrees from the output on channel
B, or the dual-pulse output can be set to quadrature mode
Not intrinsically safe
Configurable for internal or external power (active or passive):
- If internally powered, output voltage is 15 VDC ±3%, internal 2.2 kohm pull-up
- If externally powered, output voltage is 3–30 VDC maximum, sinking up to 500 mA at
30 VDC maximum
Scalable to 10,000 Hz
Can report mass flow rate or volume flow rate, which can be used to indicate flow rate or total
flow
Linear with flow rate to 12,500 Hz
Configurable polarity: active high or active low
One or two discrete outputs:
Channels B and C are configurable as discrete outputs
Can report event 1, event 2, event 1 & 2, flow direction, flow switch, calibration in progress, or
fault
Maximum sink capability: 500 mA
Configurable for internal or external power (active or passive):
- If internally powered, output voltage is 15 VDC ±3%, internal 2.2 kohm pull-up
- If externally powered, output voltage is 3–30 VDC maximum, sinking up to 500 mA at
30 VDC maximum
Configurable polarity: active high or active low
One discrete input:
Channel C is configurable as a discrete input
Not intrinsically safe
Configurable for internal or external power:
- Internal power: 15 VDC, 7 mA maximum source current
- External power: 3–30 VDC maximum
Can be used to start flowmeter zeroing procedure, reset mass total, reset volume total, reset
corrected volume total, or reset all totals
Model 2700 transmitters with intrinsically safe F
OUNDATION fieldbus outputs option board (output
option code E)
One F
OUNDATION fieldbus H1 output:
-F
OUNDATION fieldbus wiring is intrinsically safe with an intrinsically safe power supply
- Manchester-encoded digital signal conforms to IEC 1158-2