Emerson 1700 Satellite Radio User Manual


 
Installation Manual 47
Output Wiring – Model 2700 Configurable I/O Transmitters
Output Wiring – Configurable I/O SpecificationsOutput Wiring – Fieldbus/PROFIBUSOutput Wiring – Intrinsically Safe
6.5 Discrete output wiring
Discrete output (DO) wiring depends on whether you are wiring terminals 3 and 4 (Channel B) or
terminals 5 and 6 (Channel C), and also on whether you have configured the terminals for internal or
external power. The following diagrams are examples of proper wiring for these configurations:
Channel B, internal power – Figure 6-9
Channel B, external power – Figure 6-10
Channel C, internal power – Figure 6-11
Channel C, external power – Figure 6-12
Figure 6-9 Discrete output 1 – Terminals 3 & 4 (Channel B) – Internal power
Figure 6-10 Discrete output 1 – Terminals 3 & 4 (Channel B) – External power
Total load
Note: See Figure 6-13 for output
voltage versus load information.
+
3–30 VDC
Note: See Figure 6-15 for recommended
resistor versus supply voltage.
CAUTION
Excessive current will damage the transmitter.
Do not exceed 30 VDC input. Terminal current must be less than 500 mA.
+
+
Pull-up resistor or DC relay