e agsstate screen displays a numeric value
corresponding to why the generator is or is not
running. is is a diagnostic feature for OutBack
troubleshooting purposes. Press the <DOWN>
so key to view the next TIMER screen.
AGS state can be one or more of the following
numbers:
Manual Start 128
Exercise 64
Time of Day 32
Load Start 16
Voltage 24hr/2hr 8
Voltage 2min 4
SOC Start 2
An AGS state of 128 means that AGS is active
because of a manual start. More then one reason
can be true at any one time (e.g., AGS state of 20
would be load start and 2 min voltage timer). e
generator will be running any time AGS state is
greater then 0.
e agsgenfault screen displays three states:
0 or no generator fault
1 indicates the generator did not start and there
is no AC input aer ve minutes
2 indicates the generator started, but then
stopped (e.g., it ran out of fuel)
Press the <DOWN> so key to proceed.
e 24 hr vs time screen counts down the minutes,
starting at 1440, of the 24-hour voltage start set
point. Aer the battery voltage has fallen below its
24-hour set point, the timer starts and is displayed
here. Pressing the <DOWN> so key brings up
the 2hr vs time screen.
e 2hr vs time 120 min screen counts down
the 2-hour voltage start set point. Pressing the
<DOWN> so key leads to the 2 min vs time
screen.
e 2 min vs time screen counts down the
2-minute voltage start set point. Pressing the
<DOWN> so key leads to the lsstart timer
screen.
ADV/MATE/AGS/TIMERS------------
agsstate 0
DOWN AGS
ADV/MATE/AGS/TIMERS ----------
agsgenfault 0
DOWN UP
ADV/MATE/AGS/TIMERS---------
24 hr 1440 min
vs time
DOWN UP
ADV/MATE/AGS/TIMERS---------
2hr vs time 120 min
DOWN UP
ADV/MATE/AGS/TIMERS ---------
2 min 2 min
vs time
DOWN UP
ADV/MATE/AGS/PG3---------------
choose category
%SOC
PG2 START TIMERS PG4
Press the <TIMERS> so key to view the
various AGS timer-related screens.