Continental Home MATE Speaker System User Manual


 
53
When an OutBack HUB is employed, the GEN START CONTROL only aects the FX
programmed as the AGS PORT in the AGS setup. is is the HUB Port connected to the
FX with the generator start relay.
<OFF> manually overrides AGS mode. Pressing <OFF> brings up MAN-OFF indicating the
user manually shut o the generator.
<AUTO> allows the MATE to automatically start and stop the generator according to the
settings programmed in the AGS menu. Pressing <AUTO> brings up either AUTO-OFF or
AUTO-ON depending on the FX programming.
<ON> manually overrides AGS mode. Pressing it brings up MAN-ON indicating the user
manually turned the generator ON)
<OK> Returns to the point in the menu system where you entered the GEN START
CONTROL screen.
AC INPUT CONTROL
currently: USE
DROP USE OK
PRESS TWICE:
e GEN START CONTROL screen allows
changes to the Advanced Generator Start
(AGS) mode.
e AGS settings only take eect when
Advanced Generator Start is enabled (See the
AGS Mode section for more information).
NOTE: is does not control the GenAlert
function.
NOTE: To reset an AGS error, press <OFF> and then press <AUTO>.
PRESS THREE TIMES:
CHARGER CONTROL
currently: OFF
OFF AUTO ON OK
e CHARGER CONTROL screen appears.
is allows the operation of the FX battery
charger to be preset for an available AC source.
When an OutBack HUB is employed, the
CHARGER CONTROL only aects the Master
FX connected to PORT 1. e Master FX then
gives the same command to all slave FXs.