Continental Home MATE Speaker System User Manual


 
70
DC Genset
In this screen, YES means a DC generator is
present and the AGS routine, which normally
stops the generator upon the FX going to Float or
Silent, will instead stop the generator when the
vdc genstop setting is reached.
is voltage setting will terminate a Voltage Start
command when the battery voltage remains above
it for 15 minutes regardless of the DC Genset
setting. e setting can be adjusted using the
<INC> and <DEC> so keys. Press the <DOWN>
so key to view the AGS fault time screen.
AGS Fault Time is the period the generator is
given to connect to the FX system aer the AUX
output has been activated. If the generator fails
to connect and provide AC current, the MATE
displays an AGS error. e user can set this time
anywhere from 5-30 minutes by pressing the
<INC> and <DEC> so keys. Press the <DOWN>
so key to reach the cool down time screen.
ADV/MATE/AGS/SETUP
dc genset NO
DOWN UP NO YES
NOTE: If you have a generator that produces AC
voltage, maintain the NO status shown on this
screen.
ADV/MATE/AGS/SETUP-----
AGS fault time 17
minutes
DOWN UP INC DEC
VDC Genstop
ADV/MATE/AGS/SETUP-----
vdc genstop: 38.0 vdc
DOWN UP INC DEC
NOTE: e vdc genstop will turn o a generator
even if the dc genset on the previous screen says
<NO>.
Press the <DOWN> so key to go to the vdc
genstop screen.