ADV/MATE/AGS/LS-----------------
load stop 0 kw
DOWN UP INC DEC
ADV/MATE/AGS/LS----------------
load stop 1 min
delay
DOWN UP INC DEC
ADV/MATE/AGS/LS---------------
end of the LOAD START menu
UP TOP AGS
Load Stop Delay
Load Stop KW
An AGS stop command will be issued when the
total AC load of all the FXs connected to the
MATE falls below this setting for the amount of
time set with load stop delay (next screen) as long
as the generator was started due to Load Start.
is setting excludes any FX charger current
for its AC load calculation. e setting can be
changed using the <INC> and <DEC> so keys.
Pressing the <DOWN> so key leads to the load
stop delay screen.
is setting is the delay time the total system AC
load must remain below the Load Stop kw before
the generator is stopped. It is adjustable from 1 to
240 minutes using the <INC> and <DEC> keys.
Pressing the <DOWN> so key leads to the end of
the VOLTAGE START menu screen.
Pressing the <AGS> so key returns the ADV/
MATE/AGS/PG2 screen