Emerson 00825-0100-4530 Rev EC Satellite Radio User Manual


 
Quick Installation Guide
9
March 2013
To connect the transmitter
1. Verify that the power supply is disconnected.
2. Remove the terminal block cover (see picture below).
3. Pull the cable through the cable gland/conduit. For Explosion-proof /
Flameproof installations, only use cable glands or conduit entry devices
certified Explosion-proof or Flameproof. Install wiring with a drip loop where
the bottom of the loop must be lower than the cable/conduit entry.
4. To connect the wires, see the illustrations on the following pages.
5. Use the enclosed metal plug to seal any unused port.
6. Tighten the cable gland.
7. Mount the cover and make sure it is fully engaged to meet Explosion-proof
requirements (adapters are required if M20 glands are used).
For ATEX, IECEx, NEPSI, INMETRO, and TIIS installations, lock the cover with the
locking screw.
8. Connect the power supply.
NOTE:
Use PTFE tape or other sealant at the NPT threads in the Cable Entries.
Terminal block
Cable Entry, ½
in. NPT - 14 or
M20x1.5
adapter
Internal Ground
Screw
Terminals for
signal and
power supply
External Ground Screw
Termi nal
Block
Cover
Cable Entry, ½
in. NPT - 14 or
M20x1.5
adapter
Remove the orange, protective,
plastic plugs, used for
transportation.
Seal any unused port with the
enclosed metal plug.
Locking screw