Emerson 00825-0100-4530 Rev EC Satellite Radio User Manual


 
March 2013
14
Quick Installation Guide
Step 3 continued...
Type n approvals : non-sparking / energy limited power supply
RS-485 with Modbus communication
The 5300 Series RS-485 with Modbus communication transmitter version
operates using a power supply ranging from 8 - 30 Vdc (max. rating). See the
Rosemount 5300/5400 Series with HART to Modbus Converter Manual
supplement (Document No. 00809-0500-4530) for details.
Power Consumption:
< 0.5 W (with HART address = 1)
< 1.2 W (incl. four HART slaves)
NOTE:
Rosemount 5300 Series Transmitters with Flameproof/Explosion-proof output have a built-in
barrier; no external barrier needed.
Power
Supply
Field Communicator
PC
Rosemount 5300 Series
Transmitter
Fieldbus
Modem
MODBUS
POWER
HART
(RS-485)
HART to Modbus Converter
MB
MA
-
-
+
+
Ambients > 60 ºC
Use wiring rated
for min 90 ºC
MODBUS
(RS-485)
nv
erter
MB
MA
-
If it is the last
transmitter on the
bus, connect the
120
termination
resistor.
120
Power
Supply
120
RS-485 Bus
120
A
B
HART -
HART +