Click Next and the following window appears (Tank Environment).
8. In the Environment window, select Measurement Mode. If the surface is
moving up or down at rates over 40 mm/s (1.5 in./s), the Rapid Level Changes
box should also be selected. Enter the Upper Product Dielectric Constant
(icons for help functions are available to the right). For Interface Level with
Submerged Probe and Product and Interface measurement modes, it is
important that the dielectric constant value is exact.
See the Rosemount 5300 Series Reference Manual (Document No.
00809-0100-4530) for details.
Handheld HART Communicator: Fast Key Sequence [2, 1, 4]
F
OUNDATION fieldbus parameters:
TRANSDUCER_1100 > MEAS_MODE
TRANSDUCER_1100
> PRODUCT_DIELEC_RANGE
TRANSDUCER_1100
> UPPER_PRODUCT_DC
TRANSDUCER_1100
> ENV_ENVIRONMENT
Click Next and the following window appears (Volume).
9. If volume calculation is desired, choose a pre-defined Volume Calculation
Method and tank dimensions based on a tank shape that corresponds to the
actual tank. Choose Strapping Table if the actual tank does not match any of