Emerson 00825-0100-4530 Rev EC Satellite Radio User Manual


 
March 2013
28
Quick Installation Guide
Brazilian certifications
INMETRO approvals
Special conditions for safe use (X)
Letter X in the number of the certificate indicates the following special condition(s) for safe
use:
For models 530xFxxxxxxxxxE1..., 530xFxxxxxxxxxKA..., 530xFxxxxxxxxxKB... or
530xFxxxxxxxxxKC... and when the sensor area requires an EPL Ga, the installation of the
transmitter on the process wall must be done in a way that ensures the minimum
degree of protection IP67 in the connection, in compliance with regulation ABNT NBR
IEC 60529.
The intrinsically safe circuit did not withstand the dielectric rigidity tests with 500 Vca as
specified in clause 6.4.12 of regulation IEC 60079-11.
Probes covered with plastic or plastic discs should have a non-conductive area not
exceeding the maximum permitted area for the MC group, which is 4 cm
2
. Therefore,
when an antenna is used in a potentially explosive atmosphere, appropriate measures
should be taken by the user to prevent electrostatic discharge.
This equipment contains light metals. The equipment must be installed in a way that
the risk of impact or friction with other metal surfaces is eliminated.
The Ex ia version of the field device of model FISCO 5300 can be provided with a FISCO
[Ex ib] power supply when the power supply is certified with three current limiter safety
devices separately and with limitation of voltage, complying with the requirements of
the Ex ia model.
Certificate: NCC 4205/07X
Standards:
ABNT NBR IEC: 60079-0:2008/2010, 60079-1:2009, 60079-11:2009, 60079-26:2008
IEC 60079-31:2008
E2
1
Flameproof:
4-20 mA/HART model:
Ex d ia IIC T4 Gb/Ga
Ex ta IIIC T79 °C
-40 °C <
T
a
< +70 °C
U
m
: 250 V
F
OUNDATION fieldbus model:
Ex d ia IIC T4 Gb/Ga
Ex ta IIIC T69 °C
-40 °C <
T
a
< +60 °C
U
m
: 250 V
MODBUS model:
Ex d ia IIC T4 Gb/Ga
Ex ta IIIC T79 °C
-40 °C <
T
a
< +70 °C
U
m
: 250 V
1) Ordering information code for Product Certifications, see the Rosemount 5300 Series Product Data Sheet
(Document No. 00813-0100-4530) or the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530).