Emerson 00825-0100-4530 Rev EC Satellite Radio User Manual


 
Quick Installation Guide
17
March 2013
are normally configured at the factory, but can be changed if, for example, the
probe is cut in the field, or if disturbing objects in the near zone need to be
blocked out (Hold Off Distance/Upper Null Zone (UNZ)).
Handheld HART Communicator: Fast Key Sequence [2, 1, 2].
F
OUNDATION fieldbus parameters:
TRANSDUCER_1100 > PROBE_TYPE
TRANSDUCER_1100
> PROBE_LENGTH
TRANSDUCER_1100
> GEOM_HOLD_OFF_DIST
Click Next and the following window appears (Geometry).
7. Enter Tank Height, the distance from the Upper Reference Point to the Lower
Reference Point (which is the tank bottom in the screenshot above), making
sure it is as accurate as possible. See Configuration in the Rosemount 5300
Series Reference Manual (Document No. 00809-0100-4530) for details.
Set Mounting Type. Set Diameter if Mounting Type is Nozzle or
Pipe/Chamber. Set Nozzle Height if Mounting Type is Nozzle.
Handheld HART Communicator: Fast Key Sequence [2, 1, 3]
F
OUNDATION fieldbus parameters:
TRANSDUCER_1100 > GEOM_TANK_HEIGHT
TRANSDUCER_1100 > MOUNTING_TYPE
TRANSDUCER_1100 > PIPE_DIAMETER
TRANSDUCER_1100 > NOZZLE_HEIGHT