OMWT-SOFT-OPC Server Tags OMWT-SOFT-OPC Server
AnalogInput: AI
n
(OMWT-AIN5V, OMWT-AIN10V, OMWT-AIN20MA, OMWT-VIB, OMWT-
MOT)
online
(R) - indicates if the device is communicating (0 or 1)
polltime
(R/W) - how often to poll the device (in milliseconds)
nodaladdress
(R) (TCP/IP Receiver). The node address starts at 1. For
TCP/IP Receivers, the node address corresponds to the node number
for the TCP/IP connection.
repeateraddress
(R) (Wireless mode) contains the location identifier of
the OMWT-REPEAT repeater. If the sensor did not pass through a
repeater then the value is 0.
serialno
(R) - registration number of the sensor
input
(R) - current value of the sensor as percent of full scale
input.conv
(R/W) - unit conversion parameters string.
(Cal1Raw,Cal1Engr,Cal2Raw,Cal2Engr)
input.units
(R/W) default is '%'.
input.desc
(R/W) - General identification description field.
(R) indicates that the tag is readable.
(R/W) indicates that the tag is both readable and writeable. OPC Write operations