OMWT-SOFT-OPC Server .ini File Format OMWT-SOFT-OPC Server
SERVER
[Server]
- Section name.
P
ortType
- Communication medium (AUTO, OMWT-232-600, etc.).
PortNo
- Port number.
NumberDevices
- Number of devices to be polled by the server.
OfflinePollTime
- How often to poll for offline devices. Milliseconds
Tries
- No. of tries during polling before a device is marked offline.
HostAdapterCheck
- Enables/disables the detection of receiver. (0 or 1)
BaudRate
–options are: 115,200; 38,400; 19,200; or 1200. The default is
19200. Use this parameter for receivers that use a different baud rate
than the default. Make sure the value in the ini file matches the value
set in the hardware.
DefaultTempUnits
- specifies the starting units of Temperature devices
DefaultPressUnits
- specifies the starting units of Pressure devices
ConfigureEnable
– 0 – disables the Setup Menu option on the main menu.
The user then cannot make any changes to the configuration. 1 –
(default) – enable the Setup Menu option on the main menu.
SmallINI
– suppresses the listing of minor variables in order to make the ini
file smaller (useful for large networks since under Windows, an ini file
may be a maximum of 64K).
DefaultThermistorCorrID
– overrides the default thermistor Correction ID
(normally 128). All thermistors will be assigned this Correction ID
unless the ID is overriOPCn in the individual device section.
ForwardAll
– species if all packets are forwarded or only packets
associated with OMWT-SOFT-OPC’s device list get forwarded across
a TCP/IP connection. A TCP/IP client must initiate the connection to
the port specified with the ForwardPort in the [IP Addresses] section.
Each packet has the following format: sensor packet,node number,
node description, sensor label.