Omega Engineering M-4066 Satellite Radio User Manual


 
16
N
OMWT-SOFT-OPC Server .ini File Format OMWT-SOFT-OPC Server
SERVER
[Server]
- Section name.
P
ortType
- Communication medium (AUTO, OMWT-232-600, etc.).
PortNo
- Port number.
NumberDevices
- Number of devices to be polled by the server.
OfflinePollTime
- How often to poll for offline devices. Milliseconds
Tries
- No. of tries during polling before a device is marked offline.
HostAdapterCheck
- Enables/disables the detection of receiver. (0 or 1)
BaudRate
options are: 115,200; 38,400; 19,200; or 1200. The default is
19200. Use this parameter for receivers that use a different baud rate
than the default. Make sure the value in the ini file matches the value
set in the hardware.
DefaultTempUnits
- specifies the starting units of Temperature devices
DefaultPressUnits
- specifies the starting units of Pressure devices
ConfigureEnable
– 0 – disables the Setup Menu option on the main menu.
The user then cannot make any changes to the configuration. 1 –
(default) enable the Setup Menu option on the main menu.
SmallINI
suppresses the listing of minor variables in order to make the ini
file smaller (useful for large networks since under Windows, an ini file
may be a maximum of 64K).
DefaultThermistorCorrID
overrides the default thermistor Correction ID
(normally 128). All thermistors will be assigned this Correction ID
unless the ID is overriOPCn in the individual device section.
ForwardAll
species if all packets are forwarded or only packets
associated with OMWT-SOFT-OPC’s device list get forwarded across
a TCP/IP connection. A TCP/IP client must initiate the connection to
the port specified with the ForwardPort in the [IP Addresses] section.
Each packet has the following format: sensor packet,node number,
node description, sensor label.