Omega Engineering M-4066 Satellite Radio User Manual


 
OMWT-SOFT-OPC Server OMWT-SOFT-OPC Server .ini File Format
N
19
HUMIDITY
(OMWT-TEMPRH)
[Device
n
]
- S
ection name.
Address
- serial number of the sensor.
D
eviceType
- Device type. (DeviceType=HUMIDITY)
PollTime
- How often to poll the device. (ms)
Label
- Name used for the device (and Topic).
Log
- Enable/disable logging of device.
LogDecimalPlaces
- Number of decimals to create when logging.
PollSamples
- No. of samples per poll (must be odd no.) If >0 Median Filter
if <0 then Average Filter is used.
Temperature
- Indicates if sensor needs temperature compensation. (0 or
1).
DwellTime
- Time allowed to charge the probe. (ms)
PostDwell
- Time after reading to allow bus to recover. (ms)
OverSampleDwell
- Time before each over sample to charge probe. (ms)
DeadBand
- Dead band filtering value in % of full scale.
Description
- General purpose description.
Cal1Raw
- Two point calibration point 1.
Cal2Raw
- Two point calibration point 2.
Cal1Engr
- Two point calibration engineering units for point 1.
Cal2Engr
- Two point calibration engineering units for point 2.
Units
- % Relative Humidity
TempCoeff
- PPM temperature coefficient of the sensor.
TempCalib
- Temperature at which the calibration was done.
TempAddress
serial number of the temperature sensor in the probe.
MacroFilterElements
- running macro filter of the sampled data. Syntax:
[no. of elements, type] where no. of elements is number of samples to
filter; type “AVERAGE”, “MEDIAN” and “AVERAGEMEDIAN”.
Default is “=3,MEDIAN”. Example: FilterElements1=6,AVERAGE
CorrID
What CorrectionID to use with this device. Must be found in the
"Correction.INI" file that you write and keep in the same directory as
the OMWT-SOFT-OPC.ini file. 0 is the default and means no
correction; 127 is the maximum.