As a result of self-diagnosis, the message below is appeared on the LCD display of HHC,
when there are trouble in the transmitter. For each error, its cause and remedy are suggested.
Printer function
Usable only when a printer is con-
nected.
Refer to the instruction manual of
HHC.
E-2:PRINT OUT
E: PRINT
< INC >
E-1: PRINT
DATE
TIME
< CL >
E-3:PRINT OUT
PRINT OUT END
< INC >PAPER FEED
< CL >
CL
INC
INC
CL
ENT
INC
ENT
(Indicated when the printer unit is active)
YY : MM : DD
HH : MM
Paper Feed (Printer)
Without Printer Unit
E: PRINT
< INC >
NO CONNECTION
With Printer Unit
< ENT >
< ENT >
Time (Hour, Minute)
Set Year/Month/Date
F : XMTR EXT.SW
Indication on
digital indicator
CELL FAULT (C1)
CELL FAULT (C9)
(*1)
EEPROM (AMP) FLT
EEPROM (CELL) FLT
TEMP. ALARM
XMTR FAULT
Error of detecting unit
EEPROM error on amplifier side
EEPROM error on cell side
Transmitter temperature is not
within the allowable range (–45
to 90°C).
Amplifier error
Input pressure is 105% or higher
of setting range.
Input pressure is –1.25% or
lower of setting range.
Replacement of detecting unit
Replacement of amplifier
Replacement of detecting unit
Transmitter temperature is
normalized.
Replacement of amplifier
Properly controlled.
Properly controlled.
Message RemedyCause
FL-1
FL-2
FL-3
T.ALM
FL-1
OVER
Under
ZERO
(*2)
ZERO
(*2)
ZERO
(*2)
(*1) CELL FALUT (C5) to (C9) are appeared in case of “9” in 6th digit code of FKC.