Rosemount 848T
Indirect Square Root
Indirect Square Root signal conversion takes the square root of the value
computed with the indirect signal conversion and scales it to the range and
units of the PV and OUT parameters.
When the converted input value is below the limit specified by the LOW_CUT
parameter, and the Low Cutoff I/O option (IO_OPTS) is enabled (True), a
value of zero is used for the converted value (PV). This option eliminates false
readings when the differential pressure measurement is close to zero and it
may be useful with zero-based measurement devices such as flowmeters.
NOTE
Low Cutoff is the only I/O option supported by the AI block. Set the I/O option
when the block is OOS.
Block Errors
Table D-2 lists conditions reported in the BLOCK_ERR parameter. Conditions
in bold are inactive for the AI block and are given here for reference.
Table D-2. BLOCK_ERR
Conditions
PV
FIELD_VAL
100
-------------------------------


EU**@100% EU**@0%EU**@0%+=
** OUT_SCALE values
Number Name and Description
0 Other
1 Block Configuration Error: the selected channel carries a measurement that is
incompatible with the engineering units selected in XD_SCALE, the L_TYPE
parameter is not configured, or CHANNEL = zero.
2 Link Configuration Error
3 Simulate Active: Simulation is enabled and the block is using a simulated value in
its execution.
4 Local Override
5 Device Fault State Set
6 Device Needs Maintenance Soon
7 Input Failure/Process Variable has Bad Status: The hardware is bad, or a bad
status is being simulated.
8 Output Failure: The output is bad based primarily upon a bad input.
9 Memory Failure
10 Lost Static Data
11 Lost NV Data
12 Readback Check Failed
13 Device Needs Maintenance Now
14 Power Up
15 Out of Service: The actual mode is out of service.