Reference Manual
00809-0100-4697, Rev EA
October 2011
B-7
Rosemount 848T
Special Conditions of Safe Use (x):
1. The component must be housed in a suitable certified enclosure.
2. Provisions shall be made, external to the apparatus, to prevent the
rated voltage (42.2 V dc) being exceeded by transient disturbances of
more than 40%.
IECEx Certifications
I7 IECEx Intrinsic Safety
Certificate No.: IECExBAS09.0030X
Ex ia IIC T4 (T
amb
= –50 to 60 °C)
Special Conditions of Safe Use (x):
1. The apparatus must be installed in an enclosure that provides a
degree of protection of at least IP20. Non-metallic enclosures must be
suitable to prevent electrostatic hazards and light alloy or zirconium
enclosures must be protected from impact and friction when installed.
2. The apparatus is not capable of withstanding the 500V isolation test
required by IEC 60079-11: 2006 clause 6.3.12. This must be taken
into account when installing the apparatus.
IG IECEx FISCO
Certificate No.: IECExBAS09.0030X
Ex ia IIC T4 (T
amb
= – 50 to 60 °C)
Special Conditions of Safe Use (x):
1. The apparatus must be installed in an enclosure that provides a
degree of protection of at least IP20. Non-metallic enclosures must be
suitable to prevent electrostatic hazards and light alloy or zirconium
enclosures must be protected from impact and friction when installed.
2. The apparatus is not capable of withstanding the 500V isolation test
required by IEC 60079-11: 2006 clause 6.3.12. This must be taken
into account when installing the apparatus.
Table B-12. IECEx Approved Entity Parameters
Power/Bus Sensor
U
i
= 30 V U
o
= 12.5 V
I
i
= 300 mA I
o
= 4.8 mA
P
i
= 1.3 W P
o
= 15 mW
C
i
= 2.1 F C
i
= 1.2 F
L
i
= 0 L
i
= 1 H
Table B-13. IECEx Approved Entity Parameters
Power/Bus Sensor
U
i
=17.5 Vdc U
o
= 12.5 Vdc
I
i
= 380 mA I
o
= 4.8 mA
P
i
= 5.32 W P
o
= 15 mW
C
i
= 2.1 F C
i
= 1.2 F
L
i
= 0 L
i
= 1 H