Andrew ES76PK-1 Stereo System User Manual


 
Antenna
47
Check all electrical components for dirt, cracks, chips, breaks, discoloration and other
signs of deterioration and damage. A discolored, blistered, or burnt condition is evidence
of overload. Measure actual value of suspect electrical components and compare
against specified value.
Check transformer for an excessive wax deposit on the surface, discoloration, or a
pungent odor indicative of burning vanish denoting overheating or a total breakdown.
Check all terminal boards for broken or missing terminals and stripped threads. Check
tightness of lead attaching hardware.
Check each starter for a make-after-break provision through the release of one push-
button as the alternate pushbutton is pressed.
Check the relays and contactors for free operation of the armatures and contact con-
dition. The contacts are usable even though pitted, burned, worn, or discolored. The
contacts or contactor or relay assembly should be replaced only when the contact mate-
rial has been completely torn away or worn off.
Visually inspect all mechanical parts for freedom of operation without binding or inter-
ference. Check for security of all hardware and stripped or otherwise damaged threads.
Check metallic parts for corrosion, dents, distortion, and other deformation.
Check for evidence of water inside the enclosure. If any water is in evidence, check
that all seals are intact and if not, use a coating of RTV-108 (silicone rubber sealant) to
seal any exposed electrical fitting, bolt hole, or other possible water entry to the
enclosed electrical components in order to maintain a waterproof condition.
Check or change humidity absorber.
Inspection of the antenna conforms generally to standard visual inspection procedures
performed on electromechanical equipment. In addition to these procedures, perform
the following checks and visual inspections for the specific conditions noted:
Inspect all wiring and cables particularly the network to enclosure and enclosure to
mount interfaces for discoloration and burned insulation, moisture entry, corrosion, dirt,
breaks, security of connection, and other signs of deterioration. Examine connections for
dirt, corrosion, and mechanical defects. Check for loose or broken lacing and cut,
abraided, frayed, brittle, and cracked insulation.
Examine connectors for corrosion, broken inserts and stripped threads. Check con-
nector shells for distortion and dents, and contact pins for bends, misalignment or other
deformities. Check connector inserts for cracks, and carbon tracking, burns or charring
indicating arc-over.
Preventive Maintenance