Model IFT9701 Transmitter Instruction Manual 39
Configuration with a HART Communicator continued
Configuration with Communicator TroubleshootingConfiguration with ProLink IIFlowmeter Startup
To enter an internal damping value, use the menu below and follow these steps:
1. At the online menu, choose 4 (detailed setup).
2. At the detailed setup menu, choose 2 (configure field device variables).
3. At the configure field device variables menu, choose 1 (flow).
4. At the flow menu, choose 4 (flow damping).
5. Select the desired damping value.
6. Press F2 (send) to send the damping value to the flowmeter memory.
6.2.5 Flow direction
The configured flow direction (forward, reverse, or bi-directional) determines how flowmeter outputs
and totalizers will react when fluid flows through the meter. The flow direction arrow on the meter is
considered the "forward" flow direction, but the meter measures flow accurately in either direction.
To configure flow direction for the meter, use the menu below and follow these steps:
1. At the online menu, choose 4 (detailed setup).
2. At the detailed setup menu, choose 2 (configure field device variables).
3. At the configure field device variables menu, choose 1 (flow).
4. At the flow variables menu, choose 3 (flow direction), then choose the desired option. The
table below lists how outputs and totalizers are affected by the option that is chosen.
5. To send the flow direction to the flowmeter, press F2 (send).
1 Process variables
2 Diag/service
3 Basic setup
4 DETAILED SETUP
5Review
1 Flo unit
2 Flo cutoff
3 Flo direction
4 FLOW DAMPING
1 Charize sensor
2 CONFIG FLD
DEV VAR
3 Config outputs
4Device
1 FLOW
2 Density
3 Temp unit
1 Process variables
2 Diag/service
3 Basic setup
4 DETAILED SETUP
5Review
1 Flo unit
2 Flo cutoff
3 FLO DIRECTION
4 Flow damping
1 Charize sensor
2 CONFIG FLD
DEV VAR
3 Config outputs
4Device
1 FLOW
2 Density
3 Temp unit
Table 6-1 Effect of flow direction on outputs and totalizers
Fluid flow
direction
Output or
totalizer
Flowmeter configuration
Forward Reverse
Fluid flowing
in same direction
as flow arrow
on sensor
Milliamp output Output increases as flow rate
increases
Output goes to 3.8 mA
Pulse output Output increases as flow rate
increases
Output remains at 0 Hz
Internal totalizers Flow totals increase Flow totals remain constant
Fluid flowing
in opposite direction
from flow arrow
on sensor
Milliamp output Output goes to 3.8 mA Output increases as flow rate
increases
Pulse output Output remains at 0 Hz Output increases as flow rate
increases
Internal totalizers Flow totals remain constant Flow totals increase