Model IFT9701 Transmitter Instruction Manual 27
Power Supply and Output Wiring continued
Getting Started Power Supply and Output WiringMounting the Remote TransmitterBefore You Begin
Figure 4-8 Wiring to Series 3000 applications platform with I/O cable
Figure 4-9 Wiring to Series 3000 applications platform with screw-type or solder-tail terminals
Figure 4-10 Wiring to field-mount Series 3000 applications platform
(1) Paired cables with shield. Maximum length is 50 feet for 28 AWG wire (15 meters for 0,1 mm² wire),
500 feet for 22 AWG wire (150 meters for 0,3 mm
2
wire).
(2) Do not connect shields at this end.
IFT9701 pulse
output terminals
Series 3000 I/O cable
terminals
See Note 2
Earth
ground
(1) Paired cables with shield. Maximum length is 50 feet for
28 AWG wire (15 meters for 0,1 mm² wire), 500 feet for 22 AWG
wire (150 meters for 0,3 mm
2
wire).
(2) Do not connect shields at this end.
IFT9701 pulse
output terminals
Series 3000 screw-type or
solder-tail terminals
See Note 2
Earth
ground
(1) Paired cables with shield. Maximum length is 50 feet for 28 AWG wire (15 meters for 0,1 mm² wire),
500 feet for 22 AWG wire (150 meters for 0,3 mm
2
wire).
(2) Do not connect shields at this end.
IFT9701 pulse
output terminals
Series 3000 field-mount
terminals
See Note 2
Earth
ground