Mitsubishi Electronics A956GOT Stereo Equalizer User Manual


 
3.1 General Specifications
3 - 1
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
PERFORMANCE
4
NAMES OF
THE PARTS AND
THEIR SETTINGS
5
ROUGH
PRE-OPERATION
PROCEDURE
6
HANDLING
7
MAINTENANCE AND
INSPECTION
8
EMC DIRECTIVE
3 PERFORMANCE
3.1 General Specifications
The general specifications of the GOT are indicated below.
*1 Indicates the element in the distribution system between the public electricity grid and the mechanical equipment
inside the premises that the relevant device is assumed to be connected to.
Category II applies to devices such as those that draw their power supply from fixed installations.
The surge voltage withstand capability of devices with ratings up to 300V is 2,500V.
*2 This index gives a measure of the incidence of conductive materials in the environment in which the device is used.
A contamination level of 2 indicates an environment in which there is only contamination by non-conducting
materials, but due to occasional condensation, conductivity may occur.
*3 Please do not use or store GOT in an environment with atmospheric pressure greater than the atmospheric
pressure at sea level (0m).
There is a possibility errors may occur if this point is not observed.
Item Specifications
Operating ambient
temperature
Display section
A95*GOT: 0 to 40
A956WGOT: 0 to 55
Other than display section
0 to 55
Storage ambient
temperature
-20 to 60
Operating ambient
humidity
10 to 90 % RH, non-condensing
Storage ambient
humidity
10 to 90 % RH, non-condensing
Vibration
resistance
Conforms
to JIS B3502 and
IEC
61131-2
Frequency Acceleration Amplitude Sweep Count
In case of
intermittent
vibration
10 to 57 Hz --- 0.075 mm
10 times in each
of X, Y and Z
directions (for 80
minutes)
57 to 150 Hz 9.8 m/s2 ---
In case of
continuous
vibration
10 to 57 Hz --- 0.035 mm
57 to 150 Hz 4.9 m/s2 ---
Shock resistance
Conforms to JIS B3502, IEC 61131-2 (147 m/s
2
, 3 times in each of X, Y and Z directions)
Operating
atmosphere *3
No corrosive gas
Operating altitude 2000 m(6562 ft) max.
Installation site Inside control box
Overvoltage category *1 II or less
Contamination level *2 2 or less