COMMAND>INP R
INPUT STATUS REPORT
===== ====== ======
Input #1 OK -94 F
Input #2 OK -78 F
Input #3 OK -89 F
Input #4 OK -93 F
Input #5 OK -93 F
Input #6 OK -93 F
Input #7 OK -93 F
Input #8 OK -93 F
Time: 08/03/96 05:53:21
Input Operation Parameters
Type INP O at the command prompt to get a sub-menu parameters (applied globally to all inputs) that affect the
sensitivity and responsiveness of the monitored inputs.
COMMAND>INP O
INPUT OPERATIONS
===== ==========
1 = Input Dampening: Enabled
2 = Input Deadband: 1
3 = Rate of change period: 00:00:10 (hh:mm:ss)
0 = Previous Menu
Input Damping
Input damping causes the Messenger 570 to react slowly to a rapidly changing input. For example, if
temperature were being monitored and the temperature probe was moved from an ice bath to a hot water
bath, a damped input would show a gradual change in temperature every 10 to 20 seconds, rather than an
instantaneous change. This option will eliminate many false alarm situations.
COMMAND>INP O
INPUT OPERATIONS
===== ==========
1 = Input Dampening: Enabled
2 = Input Deadband: 1
3 = Rate of change period: 00:00:10 (hh:mm:ss)
0 = Previous Menu
Choose a Number>1
Input Dampening is Enabled
Change Present State? [y/n]> No
Deadband
When set to a value greater than 1, the Messenger 570 system will not report a change in input value until
the change exceeds the deadband.