Chapter 4 Rack and Optional Product Installation
4.2 Installable Racks
ETERNUS DX60 S2 Disk storage system User’s Guide -Site Planning-
55
Copyright 2012 FUJITSU LIMITED P3AM-5492-04ENZ0
Figure 4.1 Unit installation area
Table 4.2 Specifications for the unit installation area
■ Placement conditions
When determining service areas, refer to the installation document of the rack to be used.
Install air conditioning in order to ensure that the interior temperature of the rack satisfies the
temperature conditions listed in "2.1 Installation Specifications" (page 26)
and "2.4.1 Air
Conditioning" (page 30).
Specification Condition
(1) Rack front space
(From the fixed part of the ETERNUS DX Disk storage
system on the front side to the inner side of the front
rack door)
40mm or more
(2) Mount bracket length
(Size between each end of the front and rear rack
pillars)
630mm to 800mm
(3) Rack space
(From the fixed part of the ETERNUS DX Disk storage
system on the front side to the inner side of the rear
rack door)
830mm or more
(4) Rack mount kit installation area 482mm or more (recommended)
ETERNUS DX
Disk storage system
(1) (2)
(3)
(4)
Rack rear doorRack front door Rack pillars
Rack rails