Reference Manual
00809-0100-4696, Rev AA
September 2004
C-7
Rosemount 848L
57 OUT_ 3_ TAG An identifier associated with discrete output 3.
58 OUT3 The value and status of discrete Output 3.
59 OUT_ 3_
CONFIG.IO_TYPE
The transducer type of discrete sensor 11.
59 OUT_3_CONFIG.FILTER Any state change that lasts for a duration less than this filter value, will be ignored by the device.
59 OUT_3_CONFIG.FAIL_S
AFE
When the device detects a failure, OUT3 will be set to this value.
60 OUT_ 4_TAG An identifier associated with discrete output 4.
61 OUT4 The value and status of discrete Output 4.
62 OUT_ 4_
CONFIG.IO_TYPE
The transducer type of discrete sensor 12.
62 OUT_ 4_
CONFIG.FILTER
Any state change that lasts for a duration less than this filter value, will be ignored by the device.
62 OUT_ 4_ CONFIG.FAIL_
SAFE
When the device detects a failure, OUT4 will be set to this value.
63 BODY_ TEMP The value and status of electronics temperature.
64 IO_ SOFT_ REV The string contains the following fields: Major rev: 1-3 characters, decimal number 0-255 Minor rev: 1-3
characters, decimal number 0-255Build rev: 1-3 characters, decimal number 0-255 Time of build: 8
characters, xx:xx:xx, military time Day of week of build: 3 characters, Sun, Mon, Month of build: 3
characters, Jan, Feb. Day of month of build: 1-2 characters, decimal number 1-31 Year of build: 4
characters, decimal Builder: 7 characters, login name of builder
65 CLEAR_COUNTS Each bit can be written to in order to reset PULSE_ COUNT_ X. The bits numbered from 1 (LSB) to
8(MSB) will reset PULSE_ COUNT_ 1 to PULSE_ COUNT_ 8 respectively.
66 DETAILED_ STATUS Indicates the state of the transmitter.
67 MACRO_ IN_ LATCH Allows transitions of transducer block channels to be held in a specified state until the macrocycle reads
the value at least once.
68 MACRO_ EQ_ LATCH Allows transitions of transducer block channels to be held in a specified state until the macrocycle reads
the value at least once.
69 MACRO_ OUT_ LATCH Allows transitions of transducer block channels to be held in a specified state until the macrocycle reads
the value at least once.
Table C-2. I/O Transducer Parameters
Numbe
r
Parameter Description