29 TRANSDUCER_ TYPE_
2
Identifies the transducer that follows.
30 XD_ ERROR_ 2 One of the error codes defined in FF-903 XD_ ERROR and Block Alarm Subcodes.
31 COLLECTION_
DIRECTORY_ 2
A directory that specifies the number, starting indices, and DD item IDs of the data collections in each
transducer within a transducer block. For further information, please refer FF-902.
32 IN_ 5_ TAG An identifier associated with discrete input 5.
33 IN5 The value and status of discrete input 5.
34 PULSE_ COUNT_ 5 The number of pulses that have occurred on IN5 since last reset.
35 IN_ 5_ CONFIG.IO_TYPE The transducer type of discrete sensor 5.
35 IN_ 5_ CONFIG.FILTER Any state change on IN5 that lasts for a duration less than this filter value, will be ignored by the device.
35 IN_ 5_ CONFIG.FAIL_
SAFE
When the device detects a failure, IO5 will have its value set to this value.
36 IN_ 6_ TAG An identifier associated with discrete input 6.
37 IN6 The value and status of discrete input 6.
38 PULSE_ COUNT_ 6 The number of pulses that have occurred on IN6 since last reset.
39 IN_ 6_ CONFIG.IO_TYPE The transducer type of discrete sensor 6.
39 IN_ 6_ CONFIG.FILTER Any state change on IN6 that lasts for a duration less than this filter value, will be ignored by the device.
39 IN_ 6_ CONFIG.FAIL_
SAFE
When the device detects a failure, IO6 will have its value set to this value.
40 IN_ 7_ TAG An identifier associated with discrete input 7.
41 IN7 The value and status of discrete input 7.
42 PULSE_ COUNT_ 7 The number of pulses that have occurred on IN7 since last reset.
43 IN_ 7_ CONFIG.IO_TYPE The transducer type of discrete sensor 7.
43 IN_ 7_ CONFIG.FILTER Any state change on IN7 that lasts for a duration less than this filter value, will be ignored by the device.
43 IN_ 7_ CONFIG.FAIL_
SAFE
When the device detects a failure, IO7 will have its value set to this value.
44 IN_ 8_ TAG An identifier associated with discrete input 8.
45 IN8 The value and status of discrete input 8.
46 PULSE_ COUNT_ 8 The number of pulses that have occurred on IN8 since last reset.
47 IN_ 8_ CONFIG.IO_TYPE The transducer type of discrete sensor 8.
47 IN_ 8_ CONFIG.FILTER Any state change on IN8 that lasts for a duration less than this filter value, will be ignored by the device.
47 IN_ 8_ CONFIG.FAIL_
SAFE
When the device detects a failure, IO8 will have its value set to this value.
48 TRANSDUCER_ TYPE_
3
Identifies the transducer that follows.
49 XD_ ERROR_ 3 One of the error codes defined in FF-903 XD_ ERROR and Block Alarm Subcodes.
50 COLLECTION_
DIRECTORY_ 3
A directory that specifies the number, starting indices, and DD item IDs of the data collections in each
transducer within a transducer block. For further information, please refer FF-902.
51 OUT_ 1_ TAG An identifier associated with discrete output 1.
52 OUT1 The value and status of discrete Output 1.
53 OUT_ 1_
CONFIG.IO_TYPE
The transducer type of discrete sensor 9.
53 OUT_ 1_
CONFIG.FILTER
Any state change that lasts for a duration less than this filter value, will be ignored by the device.
53 OUT_ 1_ CONFIG.FAIL_
SAFE
When the device detects a failure, OUT1 will be set to this value.
54 OUT_ 2_ TAG An identifier associated with discrete output 2.
55 OUT2 The value and status of discrete Output 2.
56 OUT_2_CONFIG.IO_TYP
E
The transducer type of discrete sensor 10.
56 OUT_ 2_
CONFIG.FILTER
Any state change that lasts for a duration less than this filter value, will be ignored by the device.
56 OUT_2_CONFIG.FAIL_
SAFE
When the device detects a failure, OUT2 will be set to this value.
Table C-2. I/O Transducer Parameters
Numbe
r
Parameter Description