Emerson Process Management 2400S Transmitters Satellite Radio User Manual


 
Installation Manual 13
I/O Wiring – Model 2400S Analog Transmitters
Power Supply I/O Wiring – DP and DNI/O Wiring – ANBefore You Begin
Figure 3-1 Basic mA output wiring – Internal power
Figure 3-2 HART/analog single-loop wiring – Internal power
820 Ohm maximum
loop resistance
+
HART-compatible
host or controller
For analog communications:
820 Ohm maximum loop
resistance
For HART communications:
600 Ohm maximum loop
resistance
250 Ohm minimum loop
resistance
+