Dynacord DMM 4650 Stereo System User Manual


 
List of factory preset sequences
Sequence Nummer
S 20
Title
“stop all”
Priority
99
Stopp trigger
off
Step Command Parameter
1: Break
2: End
Sequence Nummer
S 21
Title
“Alarmtxt”
Priority
97
Stopp trigger
off
Step
Command Parameter
1: Out A1 set
2: wt In A1 High
3: Out B4 clr
4: Out B2 set
5: Out B3 set
6: Out A2 set
7: Sum= off
8: DMM= -2dB
9: Start M 00
10: wt Audio
11: End
Sequence Nummer
S 22
Title
“DIN-Alrm”
Priority
93
Stopp trigger
off
Step
Command Parameter
1: Out A1 set
2: wt In A1 High
3: Out B4 clr
4: Out B2 set
5: Out B3 set
6: Out A3 set
7: Sum= off
8: DMM= -5dB
9: Start A 20
10: wt Audio
11: End
Stops all running sequences
Description: Stops all running sequences with low priorities (all
factory presets). Upon completion the DMM 4650 returns to the
stand-by mode.
Start alarm text (message 00) once
Description: Turns the sound reinforcement system on (relay A1)
and waits for acknowledgment (input A1 = system ready). When
the system is ready, the output B4 (music program off) is opened
and B2, B3 (mandatory reception E, D) is closed. After closing
the signaling contact (A2 = alarm text running) the audio controls
are set to alarm text priority. The alarm text (M00) is given out.
After the transmission of the message is completed, the se-
quence is finished and the device returns to the stand-by mode,
i. e. all line and relay contact settings re-enter the status, prior to
the start of the sequence.
Start continuous DIN alarm (siren 1200 Hz - 500 Hz, per
second)
Description: Turns the sound reinforcement system on (relay A1)
and waits for acknowledgment (input A1 = system ready). When
the system is ready, the output B4 (music program off) is opened
and B2, B3 (mandatory reception E, D) is closed. After closing
the signaling contact (A3 = alarm signal running) the audio
controls are set to alarm text priority. The alarm signal (A20) is
outputted and runs continuously until it is stopped by a sequence
with a higher priority (e.g. S20). The control of the settings and
relay contacts is taken over by the stop sequence and upon
completion the DMM 4650 returns to stand-by mode.
37